MGE UPS Systems Power Supply Pulsar TM 30 User Manual

PulsarTM  
EX20 / EX30  
EXB20/30  
Manuel d'utilisation  
User Manual  
Manual de instrucciones  
!
+
+
%
%
Pulsar EX20  
 
note  
c this equipment has been tested and found to comply with Part 15 of the FCC Rules. These limits are designed to provide reasonable protection  
against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate  
radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio  
communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to  
correct the interference at his own expense.  
service and factory repair - call 1 - 800 - 523 - 0142  
c direct questions about the operation, repair, or servicing of this equipment to MGE UPS SYSTEMS, Inc. Customer Support Services. Include  
the part number, assembly number, and serial number of the unit in any correspondence. Should you require factory service for your equipment,  
contact MGE UPS SYSTEMS, Inc. Customer Support Services and obtain a Return Materials Authorization (RMA) prior to shipping your unit.  
Never ship equipment to MGE UPS SYSTEMS, Inc. without first obtaining an RMA.  
proprietary rights statement  
c the information in this manual is the property of MGE UPS SYSTEMS, Inc., and represents a proprietary article in which MGE UPS SYSTEMS,  
Inc., retains any and all patent rights, including exclusive rights of use and/or manufacture and/or sale. Possession of this information does not  
convey any permission to reproduce, print, or manufacture the article or articles shown herein. Such permission may be granted only by specific  
written authorization, signed by an officer of MGE UPS SYSTEMS, Inc.;  
c IBM, PC-AT, ES/9000, and AS/400 are trademarks of International Business Machines Corporation. Other trademarks that may be used herein  
are owned by their respective companies and are referred to in an editorial fashion only.  
two years warranty policy  
c MGE UPS SYSTEMS, Inc. (herein after referred to as MGE) warrants Topaz and Pulsar equipment manufactured by MGE to be free from  
defects in materials and workmanship for a period of two years from date of purchase. If within such period purchaser discovers defective item  
and promptly notifies MGE in writing, MGE shall repair or replace the item at the Company's option. This warranty shall not apply:  
v to equipment not manufactured by MGE,  
v to equipment repaired or altered by others than MGE,  
v to equipment subjected to negligence, accident, or damage by circumstances beyond MGE's control, or to improper operations, maintenance,  
or storage, or to other than normal use or service.  
With respect to equipment not manufactured by MGE, the Warranty obligations of MGE shall in all respects conform and Warranties do not cover  
reimbursement for labor, transportation, removal, installation, or other expenses which may be incurred in connection with repairs or replacement.  
Except as may be expressly provided in an authorized writing by MGE, MGE shall not be subject to any other obligations or liabilities whatsoever  
with respect to equipment manufactured by MGE or service rendered by MGE. After Sales Service Support Line: 1-800-523-0142.  
 
MGE UPS SYSTEMS  
Pulsar EX : 51032278XT/AB  
Postal address:  
MGE UPS SYSTEMS, Inc.  
1660 Scenic Avenue  
Costa Mesa, CA 92626  
714-557-1636  
51032278XT/AB  
 
ENGLISH  
IMPORTANT SAFETY INSTRUCTIONS  
SAVE THESE INSTRUCTIONS  
This manual contains important instructions for Models EX20 / EX30 / EXB20/30 that should be followed  
during installation and maintenance of the UPS batteries.  
c This equipment can be operated by any  
individual, with no previous training;  
c CAUTION: Risk of electric shock, even  
with unit disconnected from AC power  
source. Hazardous voltage still may be  
present through operation from battery.  
The battery supply should be disconnected  
at the plus and minus terminals using the  
quick disconnect connectors of the battery  
when maintenance or service work inside  
the UPS is necessary.  
c The UPS contains voltages which are  
potentially hazardous. All repairs should  
be performed by qualified service  
personnel only;  
c do not attempt to power the UPS from  
any receptacle other than a 2-pole 3-wire  
grounded receptacle;  
c the AC power receptacle should be near  
the equipment and easily accessible. To  
isolate Pulsar from AC input, remove the  
input power cord from the AC power  
receptacle;  
c if Pulsar is to be stored for a long time, it  
is recommended to recharge the batteries  
(by connecting AC power source to Pulsar,  
switch "ON" or "OFF"), once a month for 24  
hours to avoid a full batteries discharge;  
c Pulsar contains batteries that should be  
disposed of or recycled in accordance with  
local applicable laws;  
c CAUTION: do not dispose of battery or  
batteries in a fire. The battery may explode;  
c CAUTION: do not open or mutilate the  
battery or batteries, released electrolyte is  
harmful to the skin and eyes. It may be toxic;  
c CAUTION: a battery can present a risk of  
electric shock and high short circuit current.  
The following precautions should be  
observed when working with batteries:  
v remove watches, rings or other metal  
objects,  
v use tools with insulated handles,  
v wear rubber gloves, boots and safety  
glasses;  
c prior to installation, store Pulsar in a dry  
location;  
c please dispose of the packaging in  
c storage temperatures must be between  
–4°F (-20°C) and +113°F (+45°C);  
c servicing of batteries should be performed  
or supervised by personnel knowledgeable  
of batteries and the required precautions.  
Keep unauthorized personnel away from  
batteries;  
accordance with the applicable legislation.  
c do not place Pulsar near water or in  
environment of excessive humidity;  
c do not allow liquids or any foreign objects  
to get inside Pulsar;  
c do not block air vents in the back of  
c when replacing the batteries, use the  
same number and the following type of  
batteries:  
v Pulsar EX20: 8 x 12V - 6.5Ah,  
v Pulsar EX30 : 8 x 12V - 7.2Ah;  
c ~ : alternating current supply symbol;  
Pulsar;  
c do not plug household appliances such as  
hair dryers to Pulsar receptacles;  
c do not place Pulsar in direct sunlight or  
close to heat-emitting source;  
 
Pulsar EX : 51032278XT/AB  
MGE UPS SYSTEMS  
i
ENGLISH  
introduction  
In critical situations, count on MGE UPS  
SYSTEMS Pulsar EX20 and EX30  
ranging from atmospheric phenomena, to  
nearby devices generating interference such  
as elevators, photocopy machines and  
machine tools, not to mention human errors,  
like the accidental pulling out of power cords  
or tripping of circuit breakers. The  
consequences of these disturbances on  
computer systems range from data losses to  
hardware damage (power supplies, hard  
disks).  
Pulsar EX20 and EX30 are specially  
designed to protect network servers and all  
other interconnection devices that are  
sensitive to electrical disturbances.  
Pulsar EX20 and EX30 add fault-tolerance  
to the utility supplying your sensitive  
equipment.  
power  
factor  
micro  
control and  
DC to AC  
inverter  
uninterruptible power supplies (UPS). Their  
protection keeps your data intact and  
accessible.  
AC  
IN  
EMI  
filter  
corrector  
rectifier  
critical  
system  
Pulsar EX20 and EX30 UPSs ensure top  
quality power around the clock, and continue  
operations during power failures. An  
intelligent microprocessor detects any  
operating anomalies of the UPS and triggers  
an alarm if corrective action is necessary.  
In addition to the high-technology aspect of  
these UPSs, you can count on backup from  
our staff, a team of specialists, around the  
corner from you, throughout the world. It’s  
no accident that MGE UPS SYSTEMS is the  
world leader in UPS protection. The UPS  
shall provide power factor correction to  
prevent harmonic distorsions and current  
created by non-linear critical loads from  
polluting the incoming AC line.  
DC / DC  
charger  
monitored  
batteries  
c BYPASS MODE which is a default mode  
in the event of an inverter failure or overload  
in which the critical load is supplied AC  
through EMI/RFI filter:  
Pulsar EX20 and EX30 are designed as  
compact units and feature very quiet  
operation. They can be installed under a  
desk, and can also be installed in a rack  
(see "options").  
power  
factor  
corrector  
rectifier  
micro  
control and  
DC to AC  
inverter  
AC  
IN  
EMI  
filter  
critical  
system  
UPS includes:  
Pulsar EX20 and EX30 provide a stable  
supply of clean power, long back-up time  
during a utility outage (see table) and vast  
information and control possibilities  
according to the configuration selected.  
Pulsar EX20 and EX30 On-Line technology  
provides maximum protection and  
availability of your workstations, server, and  
network communication devices.  
Pulsar EX20 and EX30 offer many functions  
and characteristics designed to simplify  
power management:  
c automatic battery test carried out  
periodically. In the event of a fault, a LED  
provides advance warning for battery  
replacement;  
c batteries,  
DC / DC  
charger  
c power factor correction / battery charger,  
c DC to DC converter,  
c DC to AC Converter,  
c bypass switch,  
monitored  
batteries  
c input/output filters.  
The MGE Pulsar UPS is capable of  
providing the following modes of operation:  
c ON LINE MODE which is the primary  
mode of operation in which the critical load  
is continuously supplied by the inverter and  
protected from all forms of power line  
disturbances:  
application of Pulsar EX20 and  
EX30:  
Network servers and interconnection  
devices are very sensitive to electrical  
disturbances of all types, including outages,  
voltage sags, brownouts, spikes, etc. The  
origins of the disturbances also vary,  
 
Pulsar EX : 51032278XT/AB  
iv  
MGE UPS SYSTEMS  
options  
c front panel LEDs signal all types of faults  
and alarms;  
c Bar graph continuously indicates the  
battery charge level or the critical load  
power level;  
c UPS Manager 2 communication  
software: this software can be used for  
automatic file closing on one or more  
servers, as well as for remote UPS  
shutdown and interrogation of all Pulsar  
EX20 and EX30 operating parameters. It is  
available for Novell NetWare, Microsoft Lan  
Manager, IBM Lan Server, the main Unix  
systems on the market (SCO, AIX, HP/UX,  
OSF 1, etc.) VAX UMS and many others;  
c SNMP administration: Merlin Gerin has  
the most complete offering for the  
administration of a group of UPSs using the  
SNMP protocol with different network-  
connection modules (UM Link adaptor or  
proxy UM Agent software), supervision  
modules (dedicated software under  
Windows UM View or application for NMS  
platforms such as HP OpenView or Novell  
NMS) and a file-closing module (UM Client).  
The MGE UPS SYSTEMS offering complies  
with RFC 1628 specifications (IETF) and  
was certified by the InterWorking Labs  
during the Test Summit in June 1994;  
c SNMP card: this card, inserted into your  
unit, makes your UPS SNMP-compatible in  
any environment;  
c rack installation kit: this kit is used to  
install Pulsar EX20 and EX30 in a 19-inch  
rack;  
c UM Sensor environment measurement  
unit: compatible with SNMP and UPS  
Manager 2 Unix and OS/2, or Solution  
PacTM, this unit measures the temperature  
and the relative humidity in the room where  
the Pulsar is installed. Eight relay contacts  
are provided to transmit signals to an  
administration platform, in the form of  
voltage-free contacts to enable monitoring of  
(fire alarm, climate control fault, intrusion,  
etc.);  
c battery extension module: Pulsar  
EXB20/30 battery extension modules  
lengthen the battery time of the Pulsar  
EX20/EX30 to meet your requirements;  
c isolation transformer: input line cord  
plugs into the Pulsar EX30 output  
receptacle. Rating is 120V AC input, 208V/  
240V AC 2.75 kVA output;  
c Pulsar EX20 and EX30 are environment  
friendly: all components are recyclable and  
an electronic power-saver device reduces  
power consumption if the UPS is not active  
for a period exceeding 5 minutes while on  
battery back-up;  
c EX Driver software provides rapid startup  
of Pulsar EX20 and EX30 using the EX  
Tuner configuration module. This module  
adapts Pulsar EX20 and EX30 to user  
preferences (battery test frequency, startup  
and shutdown sequences, setting of battery  
thresholds, etc.). Operation and monitoring  
are ensured by the UPS Manager 3.1  
module operating under Windows 3.1.  
EX Driver connects to the RS 232 port on  
the Pulsar EX20 and EX30 (see  
"communication" section for further details);  
c Solution-PacTM is a CD-ROM which  
contains all the tools needed to supervise  
your UPS.  
c maintenance bypass switch: enables  
the user to continue supplying ac power to  
the load while performing routine or  
emergency maintenance.  
c status information card: this option  
provides you with 5 voltage-free contacts: on  
battery, on by-pass, low battery, load on  
UPS.  
additional communications  
options:  
c communication cables: these cables are  
used for the file-closing utilities offered by a  
number of network operating systems. They  
are available for Novell NetWare, Microsoft  
Lan Manager and Windows NT, IBM Lan  
Server, Artisoft LANtastic, Banyan Vines,  
Apple System 7, IBM AS400 and many  
others;  
Contact your dealer for further information  
on these options.  
 
Pulsar EX : 51032278XT/AB  
MGE UPS SYSTEMS  
v
software supplied with  
Pulsar EX20 and EX30  
To meet the different operating  
environments of your UPS, Pulsar EX  
includes 2 MGE UPS SYSTEMS software  
programs:  
outage or UPS problem and recording of  
events in a log file,  
associated with a UPS:  
v graphic display of the UPS,  
v remote control of the UPS and output  
receptacles,  
v during long-term power outages,  
automatic shutdown of the system and of  
the UPS, followed by automatic restart of the  
UPS (system reboot) on return of utility  
power,  
c EX-Driver software for Windows (on 3.5"  
v user alarm of problems,  
diskettes);  
v recording of events in log files,  
v automatic system shutdown and restart,  
v local or remote supervision of UPSs and  
ancillary devices,  
c Solution-PacTM network software (on CD-  
ROM).  
v PowerShareTM functions.  
Solution-PacTM for networks and  
multi-station systems  
Novell Netware, Windows NT, OS/2 Lan  
Server, SCO Unix, etc.)  
EX-Driver for Windows  
EX Driver for Windows provides  
v transmission of UPS information and  
alarms to any SNMP supervisor.  
communication with the UPS from a simple  
Windows workstation. EX-Driver is  
compatible with Windows 3.1x and Windows  
95, for communication with the UPS via a  
serial connection for various needs:  
c personalization of the UPS operating  
mode: the EX-Tuner utility, can be used to  
change certain UPS operating parameters if  
the standard factory settings are not ideal for  
the operating conditions.  
It is possible to modify the output voltage,  
battery-test frequency, startup and shutdown  
sequences, operation of automatic by-pass,  
etc.;  
c UPS monitoring from a Windows  
workstation and system safety:  
EX-Driver, UPS Manager 3 software, can  
display the UPS status, warn the user if a  
problem arises, and provide automatic  
shutdown.  
Protection by UPS is only complete and  
effective if combined with powerful software  
functions which warn users and the operator  
of any power supply problem, automate  
system shutdown, supervise and remotely  
control the UPSs. MGE UPS SYSTEMS  
created Solution-PacTM for this purpose.  
Solution-PacTM combines all these functions  
in a single CD-ROM, usable in local or  
remote mode (SNMP), and covering the  
main network environments.  
Solution-PacTM is the ideal solution for  
protecting networks and multistation  
systems.  
Solution-PacTM on a single CD-ROM  
contains everything needed to safeguard  
one or more systems and to supervise one  
or more UPSs from a local or remote station.  
Solution-PacTM includes SNMP UM-Agent,  
UM-Client system shutdown software, and  
UM-Console supervision software.  
Solution-PacTM is a powerful and upgradable  
software tool which provides all the  
supervision, control and safety functions  
The many possibilities available include:  
v supervision of operating parameters  
through a graphic interface (display of  
battery charge level, remaining battery time  
and UPS load level). These values can be  
recorded periodically in a log file,  
v messages to the user in case of power  
 
Pulsar EX : 51032278XT/AB  
vi  
MGE UPS SYSTEMS  
general contents / sommaire général / sumario general  
Pulsar EX20 / EX30 / EXB20/30 presentation  
présentation de Pulsar EX20 / EX30 / EXB20/30  
presentación de Pulsar EX20 / EX30 / EXB20/30  
Pulsar presentation  
.............................................................................................................................  
3
présentation de Pulsar  
presentación de Pulsar  
english  
.......................................................................................................................................................................  
11  
getting started / operation  
français  
....................................................................................................................................................................  
19  
27  
mise en service / exploitation  
español  
.....................................................................................................................................................................  
puesta en servicio / explotación  
 
MGE UPS SYSTEMS  
Pulsar EX : 510322378T/AB  
MGE UPS SYSTEMS  
Pulsar EX : 51032278XT/AB  
2
1
Pulsar EX20/EX30  
front view / vue avant / vista delantera  
Pulsar EX20/EX30  
rear view / vue arrière / vista trasera  
Pulsar EXB20/30  
rear view / vue arrière / vista trasera  
PLACE  
STAMP  
HERE  
19  
11  
MGE UPS SYSTEMS  
VICES  
OMER SUPPORT SER  
ATTN: CUST  
1660 SCENIC  
AVENUE  
92626  
MESA, CA  
COSTA  
12  
13  
8
21  
20  
ALK  
U-T  
SITE WIRTING  
AUL  
F
1a  
1b  
1c  
1d  
14  
Y
16  
TTER  
. BA  
EXT  
olt: 96Vdc == 20A  
V
96V == 20A  
CIRCUIT  
BREAKER  
120Vdc/40A  
!
ac OUT  
V
10  
+
22  
7a  
olt: 96Vdc == 20A  
V
ss  
r
e
pr  
I max. 30A  
ac OUT  
V
s e  
%
t
e
+
FUSE  
-T  
120V  
15A  
1e  
1f  
18  
solution-pac  
7b  
7c  
ss  
r
e
pr  
10  
6
s e  
t
e
FUSE  
120V  
-T  
15A  
%
ss  
e
pr  
r
s e  
t
e
FUSE  
120V  
-T  
2
3
15A  
CIRCUIT  
BREAKER  
30A/125V  
-T  
17  
I max 15A  
INPUT  
9
5
23  
 
Pulsar EX : 51032278T/AB  
Pulsar EX : 51032278T/AB  
MGE UPS SYSTEMS  
MGE UPS SYSTEMS  
3
4
contents  
getting started .................................................................................................................. 12  
location ...................................................................................................................................... 12  
preliminary checks .................................................................................................................... 12  
connections ............................................................................................................................... 12  
communication .......................................................................................................................... 13  
operation ............................................................................................................................. 14  
starting up with utility power present ......................................................................................... 14  
starting up with out utility power ................................................................................................ 15  
operation on battery .................................................................................................................. 16  
overload .................................................................................................................................... 17  
operating anomalies .................................................................................................................. 17  
 
MGE UPS SYSTEMS  
Pulsar EX: E-51032278XT/AB  
11  
getting started  
c connection of the Pulsar EXB20/30  
battery extension module (optional):  
v check that the button "on/off" " " on the  
front of the Pulsar EX20/EX30 is not pushed  
in,  
v disconnect the input connection cord,  
v flip the circuit-breaker of the battery unit to  
the right (position "O"),  
v connect the battery connection cord to the  
DC connector of the battery module and  
connect to the Pulsar EX20/EX30,  
v if the installation has 2 battery modules,  
connect the second cord to the DC  
connector of the second module and to the  
first module,  
v the use of connectors is strictly limited to  
connecting the battery modules to the  
Pulsar EX20/EX30. Any other connection to  
these connectors is prohibited and risks  
damaging the battery, not covered by  
warranty,  
location  
ac OUT  
V
c observe the safety rules indicated at the  
7a  
7b  
beginning of this document.  
ss  
r
e
pr  
I max. 30A  
ac OUT  
V
s e  
t
e
preliminary checks  
FUSE  
120V  
-T  
15A  
c check that the "on/off" button "  
" on the  
ss  
r
e
pr  
front is not pushed in;  
s e  
t
e
c check that rating shown on the rating label  
corresponds to the input voltage  
specification and power requirement of the  
load.  
FUSE  
120V  
-T  
15A  
ss  
e
pr  
r
s e  
t
e
FUSE  
120V  
-T  
15A  
connections  
I max 15A  
UT  
P
c connect the AC input cord to the utility  
power outlet.  
8
120V  
15A  
to computer  
loads  
ss  
r
e
r
p
e
t
s
e
utility power  
receptacle  
FUSE  
120V  
-T  
15A  
Note 1: following connection, the battery  
automatically charges, whenever plugged in.  
v to start, flip the battery circuit-breaker to  
ss  
e
r
p
r
the left (position "I"),  
e
t
s
e
FUSE  
-T  
v if your installation is operated with MGE  
UPS SYSTEMS software, update your  
battery configuration with EX Tuner.  
120V  
15A  
Note 2: the batteries will provide full back-up  
time after approximatively 8 hours of  
recharge time.  
IT  
U
ER  
T
V-  
5
I max 15A  
INPUT  
Note 3: if site wiring fault LED  
8
is lit and  
buzzer sounds, line/neutral connections are  
reversed.  
5
c connect the computer loads to output  
sockets 7a or 7b .  
 
Pulsar EX: E-51032278XT/AB  
12  
MGE UPS SYSTEMS  
communication  
c the U-Talk communication port, at the rear  
of the Pulsar, delivers information in the  
form of an RS232 series link supported by  
the communication protocol exclusive to  
MGE UPS SYSTEMS.  
option 1  
c status information card: after the card is  
optional board for installation.  
c switch ON: normal operation,  
c switch OFF: unit stops immediatly.  
installed in the rear of the Pulsar,  
communication port transmits the status  
information on a SUB-D 9-pin female  
connector using the following pinouts:  
The Solution-PacTM programs use the data  
made available by this protocol.  
5
4
3
2
1
1 - ground,  
12  
9
8
7
6
2 - remote power off,  
4 - normal operation,  
5 - common,  
6 - operation on utility power,  
7 - low battery warning,  
8 - load supplied by UPS,  
9 - operation on battery.  
standard port  
RD TD  
0V  
5
4
3
2
1
S1  
9
8
7
6
0V  
option 2  
With the EX Driver software program you  
can set up Pulsar EX to suit your user  
conditions (EX Tuner), supervise your UPS  
and safeguard your system (UPS Manager  
3.1). To install EX Driver, connect the serial  
cable supplied to COM1 to COM4 (set up by  
EX Tuner) series port of your computer  
equipped with Windows 3.1 on the one end,  
and to the serial Pulsar EX connector on the  
other end. Insert the disk and type A:\Install.  
Follow the installation instructions on the  
screen. You may then use 2 software  
programs :  
c SNMP card: after the card is installed in  
the rear of the Pulsar, the communication  
port transmits information supported by the  
SNMP protocol on an RJ45 or BNC  
connector.  
5
4
3
2
1
12  
9
8
7
6
n.c.  
n.o.  
0V  
n.o.  
0V  
n.o.  
0V  
n.o.  
Contact your sales agent for further details.  
0V  
Relay breaking capacity:  
Vmax = 25V DC  
Imax = 10mA  
v EX Tuner to set up Pulsar EX,  
v UPS Manager 3.1 to supervise and  
safeguard your system.  
n.o. : normally open,  
n.c. : normally closed.  
Note for remote power off information:  
Remove first J1 jumper on the status  
information board, then link your remote  
power off switch S1 between pins 2 and 5.  
Follow instructions from user's manual of the  
 
Pulsar EX: E-51032278XT/AB  
MGE UPS SYSTEMS  
13  
operation  
starting up with utility power present  
press button "on/off" :  
indicator lights test  
device and battery test  
7 s  
normal operation  
17 s  
automatic sequence:  
0 s  
5 s  
1a to 1f on  
1a to 1f flashing  
1a to  
1a  
1d indicating the  
remaining battery  
time percentage  
(here 50%)  
to 1d indicating the  
recharge  
percentage of the  
battery (here 50%)  
1e on  
1e off  
1f on  
1f on  
1 s beep  
several beeps  
silence  
silence  
UPS is on utility power  
output off  
output off  
your load is supported  
by the battery  
 
Pulsar EX: E-51032278XT/AB  
14  
MGE UPS SYSTEMS  
starting up with out utility power  
press "on/off" button:  
indicator lights test  
device and battery test  
7 s  
normal operation on battery  
17 s  
automatic sequence:  
0 s  
5 s  
1a to 1f on  
1a to 1f flashing  
indicating the  
remaining autonomy  
percentage  
1a to  
1a  
to 1d  
1d indicating the  
remaining battery  
time percentage  
(here 50%)  
(here 50%)  
1e on  
1e flashing  
1f on  
1f on  
1 s beep  
several beeps  
3 s beep  
1 beep every 10 s  
output off  
output off  
your load is supported  
by the battery  
UPS is on utility power  
 
Pulsar EX: E-51032278XT/AB  
MGE UPS SYSTEMS  
15  
operation on battery  
no utility power  
break in utility power  
0 mn  
warning alarm at low  
battery  
Pulsar switches off  
automatically  
x +  
ε
mn  
1a  
x mn  
1a to  
indicating the  
1a to  
off  
1c  
1d  
to 1f off  
remaining battery  
time: here, between  
75 and 87%  
1d flashing  
flashing  
1e flashing  
1e  
1f on  
1 beep every 3 s  
1f on  
1 beep every 10 s  
silence  
UPS output "off"  
your load is supported  
by the battery  
you have less than 12% battery time  
remaining: power down your load, Pulsar  
will soon switch off automatically  
return of utility power  
load charge percentage  
Note 1:  
At whatever point the utility power  
returns, Pulsar switches to normal  
operation:  
If utility power is present, hold alarm  
silence button in:  
The "function" button is to deactivate or  
activate the audio warning device when  
operating on battery, or when site wiring  
fault occured.  
1a to 1d indicating the battery  
recharge percentage: here,  
between 12 and 25%  
1a to 1d indicating the load charge  
percentage: here 50%  
Note 2:  
The "function" button allows you to force a  
transfer on bypass (push three times within  
5 seconds) and to come back on normal  
operation (push again three times within 5  
seconds).  
1e indifferent  
1f on  
1e off  
1f on  
silence  
silence  
your load is supplied by the utility power  
(on line)  
 
Pulsar EX: E-51032278XT/AB  
16  
MGE UPS SYSTEMS  
overload  
utility power present  
operating anomalies  
device fault  
battery fault  
A battery test is carried out while Pulsar, is in  
start-up mode, then automatically every 7  
days (interval times adjustable using EX  
Driver). If a battery fault is detected, the  
following occurs:  
1a flashing  
1b flashing  
1d flashing  
1d flashing  
1e off  
1e off  
1f on  
1f on  
1c flashing  
1 beep every second  
1 beep every second  
v automatic load transfer to bypass,  
v switch off Pulsar (release "on/off" button),  
disconnect from the wall socket (check input  
cord), and check that Pulsar has not short-  
circuited (disconnect all loads),  
automatic load transfer to bypass  
1e off  
1f on  
1 beep every second  
no utility power present  
v if necessary, change one of the fuses 7c ,  
recharge your battery for 8 hours.  
v re-start Pulsar.  
1a flashing  
battery low  
operation on bypass  
1a to 1f off  
1a and 1b indifferents  
1e flashing  
1f on  
1 beep every second  
1d flashing  
1e off  
Pulsar switches off automatically after a  
length of time which depends on the level  
of overload.  
1f on  
1 beep every second  
continuous beep  
Note: overload occurs if the load  
consumption is greater than the rated power  
of Pulsar.  
after the start-up sequence, if the audio  
warning device sounds continuously,  
recharge your battery for 8 hours.  
see "overload" and "device fault" section  
To acknowledge the fault, release the "on/  
off" button, temporarily disconnected Pulsar  
from the wall socket (check input cord),  
disconnect loads and re-start Pulsar.  
Note: if the previous symptoms persist,  
contact technical support.  
Note:  
This operating mode provides temporary  
inverter fault tolerance.  
 
Pulsar EX: E-51032278XT/AB  
MGE UPS SYSTEMS  
17  
 
Pulsar EX: E-51032278XT/AB  
18  
MGE UPS SYSTEMS  

KTM Motorcycle 450 EXC USA User Manual
Lenovo Personal Computer 9961 User Manual
LG Electronics Blu ray Player HB806TM User Manual
Life Fitness Home Gym G4 User Manual
Lincoln Electric Welder IM359 G User Manual
Linear Drums 5415 User Manual
Listen Technologies Microphone LBB 1900 User Manual
Logitech Computer Keyboard Tab4 101 User Manual
Marantz Stereo Amplifier PM7001 User Manual
Maytag Appliance Trim Kit DB10 User Manual