• BCnet sectional control panel with
two integrated loop interfaces
• Extends a BCnet sectional control
panel BC216-2 or BC216-3 by two
loops
• Analogue ringbus technology with
unshielded detector cabling
• Easy installation, also possible later
on
Fire is a permanent threat to life and property. There- ted within LST premises, thus guaranteeing flexible and
fore, immediate response to a fire is imperative. The reliable individual solutions.
main objective of the fire detection control panel Series
BC216 is to alarm and to react in time and, conse- Using a 32-bit multiprocessor system, the fire detection
quently, save lives and protect property. For decades control panel Series BC216 ensures topmost efficiency
LST have focused their aims to undertaking unrivaled and speed – prerequisites for saving lives and minimi-
efforts in order to realize new innovations in the security zing damage to property.
area. Research, development and production are loca-
Description
The BCnet Sectional Control Panel/Extension BCE216- The loop processing functions of the BCE216-3LG fully
3LG allows for the extension of a fire detection control correspond to the functions of a BCnet Sectional Con-
panel BCnet216 by two ADM loops. The extension is in- trol Panel BC216-2 equipped with two Loop Interfaces
tegrated into the fire detection control panel BCnet216 LIF64-1.
by installing it in a BCnet sectional control panel BC216-
2 or BC216-3 and connecting it to the GSSnet cabling The ADM loop principle offers intelligent analogue ring-
via the GSSnet interface on the extension.
bus technology with bi-directional data transfer. Each
loop provides for the software-aided administration of
The 24V supply of the BCnet Sectional Control Panel/Ex- up to 198 physical address points in a maximum of 128
tension BCE216-3LG is powered from the BCnet sectio- detector zones.
nal control panel in whose cabinet it has been installed;
it does not have a power supply or battery charger of Easy parameterisation by means of PC software en-
its own. The extension is designed as compact unit and ables you to optimally adapt the control panel to your
mounted on a pivoting sheet steel carrier.
individual requirements.
Building Safety. Building Security.
A
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
BCE216-3LG_DBL_LST_EN_0804.PDF • PAGE 1
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED
Permanent Connection
By means of a BCnet Sectional Control Panel/Extension loops. In one case, you thus have up to four loops at
BCE216-3LG, a Fire Detection Control Panel BC216-2 your disposal. In addition, a variety of peripheral de-
or BC216-3, respectively, can be extended by two vices can be connected to this device:
• Fire brigade key safe
• Transmitting device for the actuation of pagers via
ESPA protocol
• Modules for remote parameterisation and remote
maintenance via computer newtork, modem or GSM
connection
• Transmitter module for the transmission of messages
via SMS or e-mail
– and much more.
• Fire brigade control unit
• Acoustic and optical signaling devices
• External protocol printer
• Remote display and operating panels
• Remote indication unit
• Actuations
• Electronic monitoring system
Building Safety. Building Security.
A
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
BCE216-3LG_DBL_LST_EN_0804.PDF • PAGE 3
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED
Distributed Intelligence in the GSSnet
The fire detection control panel BCnet216 opens up ma- Cabling of the detectors is required only between two
nifold possibilities for the realization of specific requests neighboring sectional control panels. This clear and
of fire detection, especially in spacious buildings, high- flexible arrangement of the sectional control panel cre-
rise buildings or wide-stretched areas.
ates a powerful network. In this way, most economical
The decentralized security network that has been crea- cabling and thus efficient use of the installation expen-
ted by BCnet216 offers increased security and reduces ses is guaranteed. Larger distances between individual
the total expenses due to a much lower cabling volume. sectional control panels can be bridged through the use
The consistent ring-shaped cabling guarantees commu- of optical fiber modems or long distance modems.
nication between the sectional control panels even in
the event of a line fault.
The entire virtual control panel BCnet216 provides for
the monitoring in mid-sized and large systems, applying
A sectional control panel of the BCnet216 is parame- the same technology and the same software tools as
terised as main operating unit for the administration of with the single control panel BC216-1. This guarantees
the GSSnet, all other members can be equipped with or a minimum of training and expansion costs as well as
without a display and operating unit.
expenses of the user and thus guarantees the optimal
The system is designed modularly and can be gradually use of resources during the usable life of the building.
expanded according to future demands. The maximum
size of a BCnet216 comprises 127 network members, BCnet sectional control panels are available in wall
9700 detector zones, 9700 actuations, 999 alarming mount cabinets, as 19“ compact version and in 19“
devices, 99 transmitting devices as well as 199 logic slide-in technology.
sectors. Different interfaces are available for the con-
nection of external information devices, e.g., a facility
management system or a remote maintenance sys-
tem.
Extinguishing Control System
If required, the BCnet216 can be easily expanded to The LCnet216 is certified to EN 54-2, EN 54-4,
an extinguishing control panel LCnet216 according to EN 12094-1 and VdS as a pure extinguishing control
EN 12094-1. The panel can control up to 127 flooding panel and as a combined fire detection and extinguis-
zones in a maximum of 127 extinguishing systems.
hing control panel.
The function of the extinguishing control panel is fully in- Optionally, the LCnet216 can be implemented with full
tegrated into the fire detection control panel BCnet216, hardware redundancy.
a combined operation is therefore possible.
Specifications
Supply voltage
21 – 30 VDC
Current consumption at 24V
Idle loop current
140mA (without detectors)
typ. 300µA per detector/module
max. 300mA (at reduced line resistance)
Total loop current
Idle loop voltage
typ. 26V (Apollo/Discovery) or
typ. 29V (System Sensor/200), respectively
Loop line resistance
Number of ADM loops
Number of detector zones
Ambient temperature
Dimensions W × H × D
Weight
max. 50Ω per core
2
max. 128 per loop, max. 144 in total
-5°C to +50°C
248 × 222 × 28 (mm)
approx. 675g
Part No.
214034
Order name
BCnet Sectional Control Panel/Extension BCE216-3LG